Nominal voltage Un | 220/230/240 V |
Limited voltage | 70%~120%Un |
Nominal frequency fn | 50-60Hz+5% |
Basic current(Ib) | 5-10A |
Maximum current(Imax) | 60-100A |
Starting current(Ist) | 20mA |
Active energy constant | 1000imp/kWh |
Accuracy as Active energy to IEC62053‐21 | Class1.0 |
Power consumption in Voltage circuit | <2W <8VA |
Power consumption in current circuit | <1VA |
Operating temperature | 25℃ to+70℃ |
Storage temperature | 40℃ to+85℃ |
Insulation level | 4kV rms for 1min |
Impulse voltage withstand | 8kV, 1.2/50 μs |
Air discharge | 16kV |
Immunity to HF fields | |
80MHz to 2GHz with load | 10V/m |
100kHz to 1GHz without load | 30V/m |
Fast transient burst test | 4kV |
Meter shell Protection Rate | IP54(IEC60529) |
Insulation System Classification | Protective Class II |
Features:
--Alarm Red, it is off in normal condition, and would be on when alarming
--Trip Yellow, it is off in normal condition, and would be on when load switch disconnect.
When the following faults or alarm appear, LCD would stop on the certain code and backlight keep on.
Time Freezing: Freezing meter data according to the promissory time and interval; It can keep at least 12 times for each frozen fraction.
Instantaneous Freezing: Under improper condition, freezing current date time, all power and important measurement data; It keeps the data for last 3 times.
Appoint Freezing: In any case of older/new tariff, step tariff changeover and other situation which is necessary, the meter would freeze power and other important data on the changeover time, It keeps the data for last 2 times
Day Freezing: Store power on 0.00am for each day, total for 2 month
On Hour Freezing: Store active power for hour or half an hour, total for 96 data
Build in clock circuit with temperature compensation function, the calendar, timing, leap year can be changed over automatically. The output frequency for inner clock terminal is 1Hz. Between -25℃ to +60℃, clock accuracy is no more than ±1 s/d; Under reference temperature 23℃, clock accuracy is no more than ±0.5 s/d.
The accepted time broadcasting is no more than 5 min. No need to match with programming switch and communication password when time broadcasting. It can be set according to the inquire, and it avoid from handling in 5 min at the time when freezing or data storing.
Meter has function for LED pulse and electrical pulse output which comes direct ratio with measuring energy. Optical test output device should comply gb/t17215.211-2006, electricity test output device should comply GB/T15284-2002. It has signal output terminal for clock, and the output frequency is 1Hz
External load switch, there is a group of switch signal for meter output. Volume of switch point is AC 220V/2A. Under normal condition, switch signal for output should keep switch on of load switch, allow for power on; When reach certain condition, switch signal for output should drive operation for external load switch, power off.
Safety precautions:
* Use only isolated tools.
* Do not connect the meter to a 3 phase - 415V AC - network.
* Place the meter only in dry surroundings.
* Make sure the used wires are suitable for the max current the
meter can measure.
* Make sure the AC wires are installed correctly before activating
the current/voltage.
* Do not touch the meter connecting clamps directly with your bare
hands, with metal, blank wire or other material as you will have
the chance of an electricity shock and a possible chance for health
damage.
* Make sure the protection cover is placed after installation and
has been sealed.
* Installation, maintenance and repair should only be done by a
certified electrician.
* Never break the seals or open the front cover as this might
influence the functionality of the meter.
* Do not through, drop, kick or other physical violence to the
meter as there are high precision components inside that will break
or make the meter measure inaccurate.
* Do not mount the meter in area's with harm gas, dust, mildew or
insects or on unstable surfaces.
WUHAN RADARKING ELECTRONICS CORP.
Introduction:
Wuhan Radarking Electronics Corp. is a modern share enterprises which focusing on the smart Internet of things(IOT) /smart grid energy consumption sensor/intelligent electric safety integrated solution. It established in 2002(former name: Wuhan Radarking Co.,Ltd.)and went public on January 27, 2015 with the stock abbreviation RADARKING and stock number 831722. It owns the independent R&D center and factory which is the key recommended high-tech enterprises in Wuhan city, Hubei Province.
It mainly R&D, manufacture and sell the integrated solution of smart Internet of things(IOT) energy consumption sensor/smart grid energy consumption sensor/energy consumption information acquisition and transmission(Collector, Concentrator, Communication Module), smart electric meter, smart water meter, “RDK” energy Internet of Things(IOT) intelligent energy safety integrated solution, digital campus energy consumption acquisition(meter reading) charging management integrated solution, 4-in-1 Meter energy consumption acquisition(meter reading) charging management integrated solution, 4-in-1 Meter/All-in-One Card cloud computing total charging management integrated solution, energy consumption monitoring and analysis integrated solution, mobile phone APP(Energy Consumption, Fast E Top Up).
Principle:
It pursues “Military Academy, Military Morality, Character, Integrity”business philosophy. According to the “ Success once at a time, Advance and reliable, Customer satisfaction, Continuous improvement” quality policy, produce the military high standard products depend on the talent and technology advantages. By military character, do the man first and then work, and provide the high quality products and favorable service to the domestic and overseas clients. With the high quality products and favorable service, it has won the good reputation from clients and won the large market share. (The group users has more than 3000).
Management:
We have a high efficiency, innovative, serious management team, and the factory has already passed ISO9001-2008 QMS, and ISO14001-2004 environment management system. It has not any batch quality problem since establishment. AQSIQ( State Quality Inspection Administration) take the spot checking of our electric meter during 2009-2016, and all the meter passed the inspection. Fully proved that the production is according to our quality management system, and the product quality is stable and reliable.
Oversea Market:
Quality product performance and good reputation, our products are not only successful sales in China, but also have been exported to more than 100 countries and regions in the world, including: Mongolia, Malaysia, Bangladesh, Germany, Italy, Russia, Brazil , India, the United Arab Emirates, Saudi Arabia and other countries, the products are subject to a great welcome and praise.