120-347Vac input intelligent microwave motion sensor with UL approval
1. Features
2. Parameters
Input | Operating voltage | 108-382V AC 50/60Hz |
Rated voltage | 120/277/347V AC 50/60Hz | |
Stand-by power | ≤1.0W | |
Surge test | N—L: 1kV | |
Output | Working mode | ON/OFF 1-10V dimming |
Type of load | Inductive or resistive | |
Load capacity | 120V, 50/60Hz, 3.6A, ballast; 277V, 50/60Hz, 3.4A, ballast; 347V, 50/60Hz, 3.3A, ballast; | |
Max.surge capacity | 30A (50% Ipeak, twidth =500uS, 230Vac full load, cold start); 60A (50% Ipeak, twidth =200uS, 230Vac, full load, cold start) | |
Dim interface | 1-10V Dimming | 1-10V 0.5mA @Max. |
Sensor parameters | Operating frequency | 5.8 GHz ±75 MHz, ISM band |
Transmitting power | 0.5mW Max. | |
Hold time | 5S/30S/90S/3min/20min/+∞ | |
Stand-by dim Level | 10%/20%/30%/50% | |
Stand-by Period | 0S/5S/5min/10min/30min/1h/+∞ | |
Detection Area | 25%/50%/75%/100% | |
Daylight Sensor | 2Lux/5Lux /10Lux 25Lux /50Lux /100Lux /Disable | |
Detection Radius | Refer to detection pattern | |
Mounting height | 3-12m (Max.12m) | |
Detecting Angle | 150°(wall mounting) 360°(ceiling mounting) | |
Operating environment | Operating Temperature | -35℃...+70℃ Humidity: 85% (non-condensing) |
Storage Temperature/humidity | -40℃...+80℃ Humidity: 85% (non-condensing) | |
Certificate Standards | Safety standards | UL 60730-1 |
EMC standards | FCC part 15 | |
Environmental Requirement | Compliant to RoHS | |
Certificate | UL+CUL | |
Others | Wiring | Press-in terminals wire diameter: 10-24 AWG |
IP Rating | IP20 | |
Protection Class | Class II | |
Installation | Built-in | |
Installation dimension | Inch: 5.04 (mm: 128) | |
Package | Bubble bag+ Clapboard+ Carton(K=A) | |
Net weight | 119g | |
Life time | 5 years warranty @Ta 277V/347V full load | |
Note 1. “N/A” means not available. 2. The detection range of the sensor is related to the moving speed and size of moving object, mounting height, installation height and angle, installation site, reflectors around the sensor etc. The data in the document is typical value and tested by a 165cm person in an open indoor area. The detection range at wall mounting will be longer at ceiling mounting. Please reduce detection sensitivity at wall mounting or contact us to confirm the sensor data settings. |
3.Function
1. On-off function (Stand-by Period“0s”)
2. 2-step dimming function (Stand-by Period“+∞”)
3. 3-step dimming function (Stand-by Period“5s/5min/10min/30min/1h”)
4.Dimension (mm)
Note: During installation, the microwave antenna should be exposed as shown in the figure to prevent metal from blocking and shielding the microwave signal.
5. Wiring
*The sensor is designed for connect one load only. Connect more than one loads may damage the sensor.
6. Structure
7. Detection pattern
1)Ceiling mounting
Height: 3m Sensitivity: 100%/75%50%/25% | Height: 6m Sensitivity: 100%/75%50%/25% | Height:9m Sensitivity: 100%/75%50%/25% | Height: 12m(*) Sensitivity: 100%/75% |
Fast moving (Speed: 1m/s) | Fast moving (Speed: 1m/s) | Fast moving (Speed: 1m/s) | Fast moving (Speed: 1m/s) |
Slow moving (Speed: 0.3m/s) | Slow moving (Speed: 0.3m/s) | Slow moving (Speed: 0.3m/s) | Slow moving (Speed: 0.3m/s) |
*When installation height is 3 / 6 / 9 meters, movement signal can be detected at 25%/50%/75%/100% detection sensitivity. When at 12 meters, movement signal is only detected at 75% 100% sensitivity, no movement signal detected for 25%/50% sensitivity.
1)Wall mounting:
Wall mounted height: 2m Sensitivity: 100%/75%/50%/25% | |
Fast moving (Speed: 1m/s) | Slow moving (Speed: 0.3m/s) |
8. Dip switch settings
1. Detection Area
1 | 2 | ||
Ⅰ | ON | ON | 100% |
Ⅱ | ON | - | 75% |
Ⅲ | - | ON | 50% |
Ⅳ | - | - | 25% |
2. Hold Time
3 | 4 | 5 | ||
Ⅰ | ON | ON | ON | 5s |
Ⅱ | - | ON | ON | 30s |
Ⅲ | ON | - | ON | 90s |
Ⅳ | - | - | ON | 3min |
Ⅴ | ON | ON | - | 20min |
VI | - | - | - | +∞ |
3. Stand-by Period
6 | 7 | 8 | ||
Ⅰ | ON | ON | ON | 0s |
Ⅱ | - | ON | ON | 10s |
Ⅲ | ON | - | ON | 5min |
Ⅳ | - | - | ON | 10min |
Ⅴ | ON | ON | - | 30min |
VI | - | ON | - | 1H |
VII | - | - | - | +∞ |
4. Daylight Sensor
1 | 2 | 3 | 4 | ||
Ⅰ | ON | ON | ON | ON | 2Lux |
Ⅱ | - | - | - | ON | 5Lux |
Ⅲ | - | ON | ON | - | 10Lux |
Ⅳ | - | ON | - | 25Lux | |
Ⅴ | - | ON | - | - | 50Lux |
VI | ON | - | - | - | 100Lux |
VII | - | - | - | - | Disable |
5. Dimming brightness preset function
5 | 6 | ||
Ⅰ | ON | ON | 50% |
Ⅱ | ON | - | 30% |
Ⅲ | - | ON | 20% |
Ⅳ | - | - | 10% |
9. Initialization
1. On/Off function & 3-step dimming function: After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it turns off the light. During the initialization, the sensor is not able to detect movement.
2. 2-step dimming function: After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it dims the light to a low light level (set by stand-by dim level). During the initialization, the sensor is not able to detect movement.
10. Factory setting
Detection Area: 100%, Hold Time: 5S, Daylight Sensor: Disable, Stand-by Period: 0S,
Dimming brightness preset function: 10%
11. Application notice
1) The sensor should be installed by a professional electrician. Please turn off the power before installing, wiring, changing the setting of the DIP switch.
2) The sensor which installed in the plastic and glass lampshade will reduce the sensitivity.For every 3mm increase in thickness, the sensitivity will be reduced by 20%.
3) The dimming performance could be different from different 0-10v drivers.
4) The light sensitivity threshold is in a sunny environment, no shadow and ambient light diffuse reflection. Ambient lux level could be different in different environment, weather, climate, time-of-day and season.
5) The parameters of the sensor may need to be reconfigured in different installation environments. Please refer to the following instructions or contact the manufacturer.
6) This sensor is for indoor use only. It will affect the waterproof effect for outdoor use. Wind, rain, and moving objects around will cause false triggering.
7) The distance between any inductive sensors should be greater than 3m.
8) When the sensor is installed in a metal lamp, metal reflective surface, or a narrow enclosed environment, the microwave will be reflected repeatedly and cause false triggering. Please reduce the sensitivity or contact the manufacturer for technical support.
9) Do not place the sensor close to high-density objects such as metal, glass,concrete walls, etc, false triggering could happen.
10) Please ensure that there are no moving signals around the sensor, such as fan,DC motor, sewer pipe, air outlet, etc., the sensor may generate false trigger.
11) For a new installation environment, it is recommended to install and test 5pcs of products before batch installation.
Shenzhen Merrytek Technology Co., Ltd.
Focus on intelligent lighting control and innovate constantly!
About Merrytek
Shenzhen Merrytek Technology Co. Ltd, founded in 2011 in Shenzhen China. For more than 13 years, we have been dedicated to research electronical products for professional lighting & smart control applications. Our main products include microwave and PIR fixture sensor, human breathing detection sensor, daylight sensor, DALI & 1-10V dimmable driver, emergency pack, & IOT controls.
Why Merrytek?
Merrytek has a leading R&D team with 75 engineers, and owns pre-research team 14 members. We got over 600 patents in China and oversea countries, including 80 invention patents.
Merrytek has invested the automation line for microwave sensors in 2018. All process from plug-in, assembling, testing and packaging are completed automatically, which raise the production efficiency as well as qualified rate.
All Merrytek products are 100% tested during production, and after product is packaged, sampling test must be carried by OQC, to make sure every product received by customer can work normally.
Contact us when you have any query of Merrytek product, we will respond you fast within 24 hours in working days. Merrytek sales team is in this industry over 10 years’ experience, service over 1000 customers all over the world, we can offer you fast and professional service.
Euro, Asia & Africa market:Ray raylei@merrytek.com
America & Australia market:May may@merrytek.com
Others: sales@merrytek.com
Core Technologies Advantages
Microwave Motion Sensor
Based on principle of Doppler effect and 5.8GHz microwave detection technology for motion detecting. Currently, Merrytek developed over 200 models motion sensors which support long detection area up to 20m, 15m mounting height and outdoor use motion sensors. Those are at the leading position in our industry.
Typical products: MC and MLC series.
LifeBeing Presence Sensor Technology
As only support big range movement detecting, microwave is normally used in the places people only make a brief stay, for example, corridor, stair well, warehouse and parking lot. Merrytek use high frequency microwave and unique programming, microwave sensors are able to detect very minor movements, i.e. typing and breathing to avoid false reporting and underreporting. Merrytek provides series sensors with KNX, DALI, 485 and Bluetooth for building automation.
Application: office, classroom, meeting room, kitchen, rest room and so on.
Typical products: MSA series.
Daylight Sensor
As always, Merrytek concentrates on simple intelligent light solutions and luminaries’ construction. We successfully completed an in depth study of our patented self-adaptive LED drivers which can identify artificial light and natural light. We therefore can supply an extremely cost-effective and energy saving daylight harvesting solution for office use.
Typical products: MS series
Flicker-free DALI/1-10V Dimmable LED Driver
Replacing traditional incandescent and fluorescent lights with more efficient and longer-lasting LED-based solid-state lighting (SSL) is an undeniable trend in the lighting industry. However, since SSL fixtures are directly connected to an AC power supply, (consistent with legacy lighting), there is a risk that 100-Hz or 120-Hz flicker could occur as a result of the driving AC current’s fluctuation at the supply's output. Flicker can make people uncomfortable, causing headaches, stress and fatigue even though the human eye may not detect the flicker.
Currently, most of dimmable LED drivers have flickering issues (especially PWM types), when dimmed below 5%. Merrytek newly-developed flicker-free dimming technology can eliminate nearly all flickering and even when dimmed to 2%.
Typical products: ML and KL series.
Emergency Pack for LED Lighting
From 2016, Merrytek has dedicated to quality emergency pack for LED fittings, such as ceiling lights, tri-proof lights, down lights and panel lights. Top quality battery will be use in all our range and make sure excellent life time and good reputation.
Typical products: KE and ME series.